Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How do I address the Analog Outputs in the XLe?

address analog outputs xle
0
Posted

How do I address the Analog Outputs in the XLe?

0

Some XLes have 2 or 4 Analog outputs. They also have a HSC and PWM outputs. The HSC uses the first 8 AQ address (AQ1-AQ8) so the real world Analog outputs are addresses in Cscape as AQ9 and AQ10 (AQ12). If you are still unable to output, verify that the jumpers internal to the I/O board are set correctly. Q: Unable to read a frequency input into HSC1. A: Verify that the configuration of the XLe is configured for frequency and downloaded to the XLe. Verify that the frequency input is wired to %I19 and Ground. Verify that the controller is in run mode. Q: Unable to output a frequency out of the XLe PWM outputs. A: Verify the configuration of the PWM and AQ register settings are loaded correctly. Verify that 24 VDC is wired between V+ and Ground. Verify that the controller is in run mode Q: I am unable to get a clock pulse out of output %Q1. I configured the output to stepper and have followed the instructions in the manual. All that appears to happen is that %Q1turns on. A: The XLE shoul