How do I address the Analog Outputs in the XLe?
Some XLes have 2 or 4 Analog outputs. They also have a HSC and PWM outputs. The HSC uses the first 8 AQ address (AQ1-AQ8) so the real world Analog outputs are addresses in Cscape as AQ9 and AQ10 (AQ12). If you are still unable to output, verify that the jumpers internal to the I/O board are set correctly. Q: Unable to read a frequency input into HSC1. A: Verify that the configuration of the XLe is configured for frequency and downloaded to the XLe. Verify that the frequency input is wired to %I19 and Ground. Verify that the controller is in run mode. Q: Unable to output a frequency out of the XLe PWM outputs. A: Verify the configuration of the PWM and AQ register settings are loaded correctly. Verify that 24 VDC is wired between V+ and Ground. Verify that the controller is in run mode Q: I am unable to get a clock pulse out of output %Q1. I configured the output to stepper and have followed the instructions in the manual. All that appears to happen is that %Q1turns on. A: The XLE shoul