Will equipment that runs on 230 volt 3 phase run on a 120208 3 phase meter box.?
Are you sure its 3 phase? As in industrial? If it is 3 phase a 230v motor/starter/whatever will run from 208v 3 phase. Electric motors are wired the same for the 208v-240v range. Tie the motor leads 4-5-6 together. The wire pairs of 1-7, 2-8, 3-9 tie to the 3 incoming wires. If the motor turns the wrong way you swap the incoming leads on two of your wire pairs. If that doesn’t help try e-mailing me or contact and industrial electrician. miketyson26@yahoo.