Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Will equipment that runs on 230 volt 3 phase run on a 120208 3 phase meter box.?

0
Posted

Will equipment that runs on 230 volt 3 phase run on a 120208 3 phase meter box.?

0

Are you sure its 3 phase? As in industrial? If it is 3 phase a 230v motor/starter/whatever will run from 208v 3 phase. Electric motors are wired the same for the 208v-240v range. Tie the motor leads 4-5-6 together. The wire pairs of 1-7, 2-8, 3-9 tie to the 3 incoming wires. If the motor turns the wrong way you swap the incoming leads on two of your wire pairs. If that doesn’t help try e-mailing me or contact and industrial electrician. miketyson26@yahoo.