Will DirectSOFT programming software connect to the GE Series 1 CPUs?
DirectSOFT will recognize the GE Series 1+ CPUs but not the GE Series 1 To identify which CPU you have • Disconnect power from the base • Remove the CPU from the base • Look for the part number on the label If you have a part number of IC610CPU101 or 104 – You have a GE Series 1 – DirectSOFT will NOT connect If you have a part number of IC610CPU105 or 106 – You have a GE Series 1+ – DirectSOFT will connect. DirectSOFT will also connect to the TI305 CPU 325, 325S, 330, 330S, and 335. A D3-DCU (Data Communications Unit) is required when connecting to any of these CPUs with DirectSOFT.