Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Why does one lkWp SRT PVI consist of 8 strings with 12 SRT per string ?

pvi srt String strings
0
Posted

Why does one lkWp SRT PVI consist of 8 strings with 12 SRT per string ?

0

There are 2 reasons: The 12 SRT produce a safety voltage under 75VDC during the installation only, like a model railway. As this voltage is harmless, the roofer is allowed to connect the SRT during laying the roof and to connect the strings to the SSB. A characteristic of PV systems is that the weakest element determines the power output. A CPVI which is connected in series fails totally when just one element or a connector fails. In a SRT PVI always 2 strings run parallel, so if one element or a connector fails, 50% of the output is still available. You also see immediately if a string has failed if any of the red indication lamps is off.