Liebert uses R134a in the pumped refrigerant circuit. It is an environmentally friendly refrigerant with no ozone depletion potential and very modest global warming potential. This is an off-the-shelf refrigerant that in the Liebert XD system operates at low pressure and becomes a gas at room temperatures should a leak occur. At typical operating conditions, the temperature in the circuit is 55-60F and the pressure is 60-80 psig. Due to the phase changing of the refrigerant in the circuit, the pressure and the temperature does not change during the refrigeration cycle.