Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Where do I terminate that bare bond wire?

Bond wire
0
Posted

Where do I terminate that bare bond wire?

0

The bare wire in Type AC cables is a bonding wire to enhance the ground fault capability of the interlocked outer metal armor. It does not have to be terminated like a bare grounding conductor because that is not its function. This bare bond wire may be trimmed off to the same length as the armor, or, brought up and over the red anti-short bushing and back wrapped over the armor.