Where do I place the user alarm setting?
That would depend upon the pressure reading in the room. If the alarm point is set too close to the actual room pressure you will experience alarms. Don’t forget CDC states -0.01″ is an acceptable negative reading. Many people set the alarm point at neutral (.000″) or at plus 0.001″ reading. The neutral point gives them warning the plus reading is noncompliance.