Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Where can the temperature and pressure relief valve be terminated?

0
10 Posted

Where can the temperature and pressure relief valve be terminated?

0
10

The temperature and pressure relief valve (minimum 150 psi rated) shall be taken full size (minimum ¾”inch) to the exterior of the dwelling or building. Most manufacturer installation instructions allow for a maximum 30 foot distance with no more than 4-90 degree elbows in this line. The temperature and pressure relief line shall be sloped from the vessel to the exterior at ¼” per foot using straight lengths of piping instead of coils.