Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

When calculating head losses, what Hazen-Williams friction coefficient should I use for concrete pressure pipe?

0
Posted

When calculating head losses, what Hazen-Williams friction coefficient should I use for concrete pressure pipe?

0

The AWWA M9 Manual for Concrete Pressure Pipe recommends, in Chapter 3, Hydraulics, the following Hazen-Williams friction coefficients: Pipe Diameters 16″ thru 48″: 140 Pipe Diameters 54″ thru 108″: 145 Pipe Diameters 114″ and larger: 150