Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Whats the acceptable voltage drop between the fire alarm control panel and the end-of-line resistor?

0
Posted

Whats the acceptable voltage drop between the fire alarm control panel and the end-of-line resistor?

0

CAN/ULC-S524 Section 3.4.4 states: “The voltage drop and power dissipation on any circuit shall not prevent the proper operation of that circuit and shall be in accordance with the manufacturer’s installation instructions.” This can vary significantly between manufacturer, panel models, and modules. That’s why it’s really important for you to be able to reference the installation manual for the panel you’re testing. You’ll also be able to determine if the correct gauge of wire has been used for the estimated length of the run.