What types of cables can be placed in MaxCell?
• Inside or Outside Plant Cables • Communications Cables: Fiber Optic, Coax, Twisted Pair, Copper, Cat 5, etc. • Utility Cables: Power, Control, Lighting What is the maximum fill ratio recommended when using MaxCell? A. The recommended maximum fill ratio is 45%. Above that level, testing and experience has shown a marked increase in cable pulling tensions. Remember to check local codes for allowable maximum fill ratio. How long can MaxCell be pulled? A. The distance MaxCell can be pulled is affected by the type of duct structure, the number of horizontal or vertical changes within a run, the presence of incumbent cables or innerduct, and the number of sweeps or bends. The longest pull to date is 6,000 feet on multiple occasions. In multiple cell MaxCell packs, is there a particular order for installing the cables? A. We recommend installing cables starting with the middle cell in a 3-cell configured product. This allows ease of entry into other cells at later dates. In occupied conduit