Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What should you pay attention to with feedforward control on control block FB58 “TCONT_CP”?

0
Posted

What should you pay attention to with feedforward control on control block FB58 “TCONT_CP”?

0

Description: With control block FB58 “TCONT_CP” there might be incorrect behavior of the complete block if the “DISV” input is used. Using feedforward control should therefore always be avoided and the “DISV” input should be set permanently to “0”. Important: This is not normal behavior and only occurs under certain conditions. However, it results in the complete control block no longer working properly. Note: The behavior described above has been cleared in STEP 7 version V5.3 and higher.