Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What should a water purveyor do to control cross-connections and protect their public water systems against backflow?

0
Posted

What should a water purveyor do to control cross-connections and protect their public water systems against backflow?

0

A water purveyor should ensure that a proper backflow preventer is installed and maintained at the water service connection to each system or premises that poses a hazard to the public water system (premise isolation). Generally, this would include water service connections to each dedicated fire protection system or irrigation piping system; premises with an auxiliary or reclaimed water system; industrial, medical, laboratory, marine or other facilities where objectionable substances are handled in a way that could cause pollution or contamination of the public water system; premises exempt from Part 7 (Plumbing) of the Ontario Building Code and premises where an internal backflow preventer required under the Ontario Building Code is not properly installed or maintained; classified or restricted facilities; and tall buildings. Zone protection within a facility may be required in addition to premise isolation, a requirement in order to protect users of the facility.

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123