Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What provisions must be made available when a second party is suppling the generator for the operation of an EHPA during an emergency?

0
Posted

What provisions must be made available when a second party is suppling the generator for the operation of an EHPA during an emergency?

0

The provisions vary according to whether the generator is trailer mounted or skid mounted. The generators, in both cases, require some type of tie down system and the system is different according to which of the above type is supplied. If the supplying party cannot guarantee which type will be supplied, then it becomes necessary to prepare for both conditions. Next, it needs to be determined if the generator to be supplied is capable of meeting the wind and missile impact criteria required by the FBC. If the generator can meet the wind and missile impact criteria, then nothing else is required. If the generator cannot meet the wind and missile impact criteria, then it becomes necessary to provide a generator shelter that shall meet the criteria.