Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What percentage of total transformer capacity is available in an open delta system?

0
Posted

What percentage of total transformer capacity is available in an open delta system?

0

The 3 phase capacity of an open delta system is 87% of the total transformers in the circuit. An example would be: two 50 KVA single phase transformers connected in open delta. The 3 phase capacity would be the sum of the two units multiplied by .87 or 100 KVA x .87 which would equal 87 KVA. In the event the third transformer of 50 KVA was added to this open delta bank to form a closed delta, the 3 phase capacity would then be the sum of the three transformers in the bank or 150 KVA.