Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What mounting orientation should be used to install a safety valve?

0
Posted

What mounting orientation should be used to install a safety valve?

0

Installing a safety valve in any position other than with the spindle vertical and upright may adversely affect performance and lifetime. Section I – PG-71.2 – Every safety valve or safety relief valve shall be connected so as to stand in an upright position, with spindle vertical. EXCEPTION: PEB-15.3 (Electric Boilers) Safety and safety relief valves shall be mounted in accordance with PG-71.2 with the spindle vertical. Electric boilers that do not exceed the diameter, volume, or pressure limits of PMB-2, may have a spring-loaded safety or safety relief valve(s) installed in other than the vertical position, provided that: • The valve design is satisfactory for such position • The valve is not larger than NPS (DN20) • The maximum angle of deviation from vertical does not exceed 30 deg • The nozzle location is such that no material that could interfere with the operation of the valve can accumulate at the valve inlet • The discharge opening of the valve body and discharge piping is ori