What mounting orientation should be used to install a safety valve?
Installing a safety valve in any position other than with the spindle vertical and upright may adversely affect performance and lifetime. Section I – PG-71.2 – Every safety valve or safety relief valve shall be connected so as to stand in an upright position, with spindle vertical. EXCEPTION: PEB-15.3 (Electric Boilers) Safety and safety relief valves shall be mounted in accordance with PG-71.2 with the spindle vertical. Electric boilers that do not exceed the diameter, volume, or pressure limits of PMB-2, may have a spring-loaded safety or safety relief valve(s) installed in other than the vertical position, provided that: • The valve design is satisfactory for such position • The valve is not larger than NPS (DN20) • The maximum angle of deviation from vertical does not exceed 30 deg • The nozzle location is such that no material that could interfere with the operation of the valve can accumulate at the valve inlet • The discharge opening of the valve body and discharge piping is ori