Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What kind of redundancy is possible for fieldbus system?

0
Posted

What kind of redundancy is possible for fieldbus system?

0

According to the IEC61158 specifications, redundancy is possible in H1 bus segments. However, manufacturers have chosen not to implement this capability, on the grounds of cost, bearing in mind that the number of devices on a single segment may be fairly limited in critical process applications (maybe only 4 or 6 – one or two control loops-worth). If devices were to offer redundant fieldbus connections, there would also be discussion about how far up the protocol stack the redundancy should go within the device; even to the level of duplicating the internal microprocessor and maybe the sensor or actuator. It is very difficult to resolve these questions in a way satisfactory for a wide range of applications. It can be argued that if a particular measurement or actuator is so vital, it is better to simply add a complete duplicate device, and connect it to a different fieldbus segment. (Note that failures within a fieldbus device should not prevent continued communication by other devices