What is the wind load capacity of Tridipanel?
The brief synopsis which follows, is from the test results report dated 1994 from Dade County, Miami Florida pertaining to the wind load capacity of Tridipanel. Three typical Tridipanels 4′ wide and 10′ high with 1 ½” of shotcrete on each face were installed vertically, side-by-side, on a concrete slab, several inches in front of a rigid backup wall with space between the panels and the backup wall. The panels were tested per static-wind load test (PA202-94 manner of testing). Summary: The specimens tested herein were fully tested in accordance with the Dade County Building Code Compliance Office Protocols PA 201-94,PA 202-94 and PA 203-94. No failures occurred to the specimens nor their fastenings nor anchorage. The products described in this report comply with SFBC Sections 2309 and 2315. The panels tested at 126 lbs per Sq. Ft. pressure, which represents over 225mph-wind factor. Please see wind load chart Exhibit 1.