What is the timeframe for operator actions used to satisfy a diversity requirement?
There is no regulation concerning acceptable timeframes. It is commonly believed that 30 minutes is a reasonable lower limit for operator action, but requirements are assessed on a case by case basis. The Highly-Integrated Control Room- Human Factors task working group (TWG), consisting of various NRC staff members and industry participants, is working on establishing an acceptable timeframe for operator actions.