Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the specification of the Current Transformers used with the AIM Filter?

0
Posted

What is the specification of the Current Transformers used with the AIM Filter?

0

The current transformers (CT’s) require to be chosen with great care as they significantly influence the performance of the AIM Filter. Ratio: 2000:1 (alt. 1000:0.5 ; 3000:1.5) Frequency Range: 50-400Hz Class: 1 Burden: 5VA Type: Ring or Split Core Safety: Fitted with voltage clamping diodes Please ask for our Current Transformer technical data sheet.