What is the recommended minimum bend radii when installing copper OSP cabling?
The recommended minimum bend radii for corrugated single shield tape designs is 12 times the cable diameter. The recommended minimum bend radii for corrugated dual shield tape designs is 15 times the cable diameter. The recommended minimum bend radii for flat, single, shield tape designs is 15 times the cable diameter.