Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the proper height to mount a fire extinguisher, as per NFPA 10 guidelines?

0
Posted

What is the proper height to mount a fire extinguisher, as per NFPA 10 guidelines?

0

A. Extinguishers with a gross weight not exceeding 40 pounds should be installed so that the top of the extinguisher is not more than 5 feet above the floor. Extinguishers with a gross weight greater than 40 pounds, except wheeled types, should be installed so that the top of the extinguisher is not more than 3 feet above the floor. In no case can the clearance between the bottom of the extinguisher and the floor be less than 4 inches.

0

A. Extinguishers with a gross weight not exceeding 40 pounds should be installed so that the top of the extinguisher is not more than 5 feet above the floor.Extinguishers with a gross weight greater than 40 pounds, except wheeled types, should be installed so that the top of the extinguisher is not more than 3 feet above the floor.In no case can the clearance between the bottom of the extinguisher and the floor be less than 4 inches.