Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the maximum transmission distance of the Digi-Pulse series of sensors?

0
Posted

What is the maximum transmission distance of the Digi-Pulse series of sensors?

0

The Digi-Pulse series of sensors are suitable for long transmission distances; however the maximum useable distance is a function of the capacitance of the type of cable used. For example using a PVC insulated cable (Alpha PN 7633 or equivalent) at a transmission distance of 3000 feet, the rise time of the pulse will increase from approximately 0.3 microseconds to 300 microseconds. Using a Teflon insulated cable (Alpha PN 2814/3 or equivalent) instead of the PVC cable, the transmission distance could be increased to approximately 10,000 feet with the same rise time of approximately 300 microseconds.

0

The Digi-Pulse series of sensors are suitable for long transmission distances; however the maximum useable distance is a function of the capacitance, inductance, and resistance of the type of cable used. With communication cables such as UTP #24AWG the outputs of the Digi-Pulse sensor family can be extended up to 100 meters.