Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the control voltage for the PST softstarter?

CONTROL PST softstarter voltage
0
Posted

What is the control voltage for the PST softstarter?

0

The PST softstarter has three different voltages levels on it. The Three phase Motor voltage, the (120-220)Vac Supply voltage, and the 24Vdc control voltage. The 24Vdc can be supplied extenally by removing the jumper between terminal 8 & 9. Then put your Negative on Terminal 8 and and use the Positive as a signal to the Stop/Start terminals. • Q: Why does my softstarter have a fault for an SCR A: Possibility the the motor is coasting to a stop and the Regeneration voltage is induced back into the load side of the softstarter. Check the SCR’s without power to see if they are shorted.