Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the control logic between the energy saver and auxiliary cooling coils and the compressor(s)?

0
Posted

What is the control logic between the energy saver and auxiliary cooling coils and the compressor(s)?

0

Energy Saver/Auxiliary Chilled Water Cooling will be available whenever the incoming water supply is below the setpoint of the Water Sensing Changeover Thermostat. The Energy Saver/Auxiliary Chilled Water mode will operate only in a two (2) degree range. The range is between the return air setpoint plus deadband and two (2) degrees above this. If the temperature rises above this range, Energy Saver/Auxiliary Chilled Water Cooling will be inhibited for one (1) hour and DX cooling only will be available. After one (1) hour, it will try Energy Saver/Auxiliary Chilled Cooling again. The chilled water valve proportionally opens 10% for each 0.1ยบ F above the Temperature Setpoint plus Temperature Deadband. The chilled water valve responds to a change of the return air temperature after each adjustment period. Then a change is made to the setpoint, the chilled water valve will delay its response for five (5) minutes, then will respond after each adjustment period. If the temperature is consist

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123