Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the advantage of using Forane® 427A instead of R-407C for the retrofit of existing R-22 equipment?

0
Posted

What is the advantage of using Forane® 427A instead of R-407C for the retrofit of existing R-22 equipment?

0

When retrofitting existing R-22 equipment with Forane® 427A, an oil change is recommended (from mineral or alkylbenzene to polyolester) but thanks to Forane® 427A’s high tolerance to residual original oil, in most cases only one oil draining operation is necessary. There is no need for long and costly rinsing of the circuit. This is not the case with R-407C which can only tolerates traces of original oil in the POE lubricant. Forane® 427A is consequently a much simpler retrofit solution which additionally can, in most cases offer better performances than R-407C.