Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the advantage of using Forane® 427A instead of R-404A for the retrofit of existing R-22 equipment?

0
Posted

What is the advantage of using Forane® 427A instead of R-404A for the retrofit of existing R-22 equipment?

0

When retrofitting existing R-22 equipment with Forane® 427A, no modification of the installation is necessary which is not the case with R-404A requiring in most cases a replacement of the expansion valve, redesign of the liquid line, and sometimes modification of the heat exchangers or compressors. Forane® 427A is consequently a much simpler retrofit solution it has a much lower GWP than R-404A.