Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is required for fire alarm plan review submittal?

alarm Plan review submittal
0
Posted

What is required for fire alarm plan review submittal?

0

The Fire Alarm Permit and Plan Review Procedures must be followed. A minimum of 3 sets of design drawings, drawn to a recognized architects scale must be submitted, stamped, signed and dated with either a Texas Fire Alarm Planning Superintendent (APS) registered with the submitting company, or a Professional Engineer registered in Texas whose major discipline is Fire Protection Engineering (FPE). A minimum 2 copies of battery and voltage drop calculations as well as manufacturer’s specifications for all equipment installed must be provided. The Fire Alarm Plan Review Fee must be paid prior to plan review. A completed Fire Alarm Plan Review Request form (MS Word) (Adobe PDF) must also be submitted.