Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is end point and best straight line fit Calibration methods?

0
10 Posted

What is end point and best straight line fit Calibration methods?

0
10

In the end points match calibration method, the 4 mA and 20mA corresponds to the lower temperature and higher temperature of the specified range. For example for the 0-400 oC range, the 4mA = 0 oC and 20mA = 400 oC. Where as, in case of the best straight line fit calibration method, the non linearity of the thermocouple or Pt -100 curve is distributed on either side of the straight line drawn between 4 and 20mA. This will minimize the 4-20mA error due to non-linearity of the curve.