What enhanced management features are needed in order to claim the ajustment factor offered in table 3 of ADL2A?
The adjustment factor is available for “automatic monitoring and targeting with alarms for out of range values”. This means:a complete installation that measures, records, transmits, analyses, reports and communicates meaningful energy management information. It would normally include primary and secondary metering to the standard set out in TM39, with automatic meter reading, transmission and storage of the consumption data to a central point and software that analyses the consumption data, produces reports to predetermined criteria and communicates the resulting information to the energy manager. The key element over and above the provisions set out in paragraph 43 of ADL2A is the analysis and reporting software. The checks the software carries out and the alarms it raises will be a function of the particular installation, but its purpose should be to immediately highlight any unexpected change in energy demand that might indicate energy wastage. The software should also facilitate b