Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What electrical setup does a typical installation of LATICRETE Floor HEAT require?

0
Posted

What electrical setup does a typical installation of LATICRETE Floor HEAT require?

0

LATICRETE Floor HEAT installations that require less than 100 square feet of coverage will require the following: Dedicated 20 Amp circuit GFCI Breaker 1,2, or 3 junction boxes: This will depend on the heating system and the number of controls being installed to regulate it. Each control will require 1 junction box. (Size may vary.) Multiple mat installations will require an additional junction box near floor level as well. Further details should be provided on the installation layout. LATICRETE Floor HEAT installations that require more than 100 sqft of coverage and that EXCEED a Total of 16 Amps will require the following: Dedicated Circuit (to accommodate the Total Load) GFCI Breaker Contactor OR Multiple Controls (Multiple Controls installations will require the room to be split into more than one zone.) Number of junction boxes will vary. This will depend on the heating system and the number of controls being installed to regulate it. Each control will require 1 junction box. (Siz