WHAT DO I NEED TO DO TO SET THE PARAMETERS OF THE CONTROLLERS SO THAT THEY ARE ABLE TO READ TEMPERATURE WITH EWHS 310 PROBES?
Parameters should be set as shown in the following table: DEVICE PROBE PARAMETERS EM300LX EWHS 310 H00=020, also H00=420 H03=-30, also H03=-10 H04=70, also H04=70 IC 912, 912LX EWHS 310 H00=020, also H00=420 IC 915, 912LX H03=-30, also H03=-10 H04=70, also H04=70 EWDR 902 EWHS 310 Lci=-10 EWDR 905 Hci=70 EWPC 902 EWPC 905 EWHS 310 Lci=-10 EWPC 902/S Hci=70 EWPC 905/S EWTR 910,920,930,940 Available in: