WHAT DO I NEED TO DO TO SET THE PARAMETERS OF THE CONTROLLERS SO THAT THEY ARE ABLE TO READ EWPA PRESSURE PROBES?
Parameters should be set as shown in the following table: DEVICE PROBE PARAMETERS EM300LX EWPA 007 H00=420 H03=-0,5 H04=7 EWPA 030 H00=420 H03=0 H04=30 IC 912, 912LX EWPA 007 H00=420 IC 915, 912LX H03=-0,5 H04=7 EWPA 030 H00=420 H03=0 H04=30 EWDR 902 EWPA 007 Lci=-05 EWDR 905 Hci=7 EWPC 902 EWPC 905 EWPA 030 Lci=0 EWPC 902/S Hci=30 EWPC 905/S EWTR 910,920,930,940