WHAT DO I NEED TO DO TO SET THE PARAMETERS OF THE CONTROLLERS SO THAT THEY ARE ABLE TO READ EWHS HUMIDITY PROBES?
Parameters should be set as shown in the following table: DEVICE PROBE PARAMETERS EM300LX EWHS 280 H00=420, also H00=020 H03=20, also H03=0 H04=100, also H04=100 EWHS 300 H00=420 H03=0 H04=100 EWHS 310 H00=020, also H00=420 H03=0, also H03=20 H04=100, also H04=100 IC 912, 912LX EWHS 280 H00=420, also H00=020 IC 912, 912LX H03=20, also H03=0 H04=100, also H04=100 EWHS 300 H00=420 H03=0 H04=100 EWHS 310 H00=020, also H00=420 H03=0, also H03=20 H04=100, also H04=100 EWDR 902 EWHS 280 Lci=20 EWDR 905 Hci=100 EWPC 902 EWPC 905 EWHS 300 Lci=0 EWPC 902/S Hci=100 EWPC 905/S EWTR 910,920,930,940 EWHS 310 Lci=20 Hci=100