Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are typical extinguishment times for INERGEN® systems?

extinguishment SYSTEMS times
0
Posted

What are typical extinguishment times for INERGEN® systems?

0

For a flammable liquid fire (2.5 sq. ft. steel pan, 6″ deep with a 2’ minimum layer of n-heptane with a 2″ free-board), extinguishment is typically 17 to 21 seconds, average of 19 seconds. For a Class A fire (Class A Crib, four layers of six, trade size 2″ x 2’ X18″ long kiln-dried spruce or fir lumber having a moisture content between 9% and 13%) extinguishment is typically 22 to 27 seconds, average of 24.25 seconds.