Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the ULC standards for the time delay on a flow switch?

delay flow Standards Switch time ULC
0
10 Posted

What are the ULC standards for the time delay on a flow switch?

0
10

The ULC Standard we have to reference to answer this question is CAN/ULC-S524-06 (Installation Standard for Fire Alarm Systems). Sentence 5.3.2 states: “Waterflow devices incorporating an adjustable time delay shall be set with a sufficient delay not exceeding 90 s to reduce the possibility of a false indication (e.g. caused by water hammer).” The single letter “s” refers to “seconds”.