Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the typical pressures for discharge and suction?

Discharge pressures suction
0
10 Posted

What are the typical pressures for discharge and suction?

0
10

Discharge pressures range between 215 to 250 PSI. Suction pressures range from 60 to 70 PSI. What are the typical temperatures for superheat and sub-cooling? Sub-cooling temperatures range between 10 to 12 degrees F. Superheat temperatures range between 10 to 14 degrees F. with unit return air at 68 to 74 degrees. Are traps required in refrigerant piping run with air cooled units? Yes, trapping is required on both the discharge and/or suction lines. Discharge lines, also called hot gas lines, should be trapped at the top (inverted) and bottom, as well as every 15-20 feet of vertical rise as applicable. Suction lines should be trapped in a similar fashion. How much steam is generated by the Nordec humidifier? Can it be adjusted? The amount of steam generated depends on the model of humidifier you have in your Data Aire unit. To determine the model number, locate the product description label on the Nortec humidifier. Match the model number to the table below to determine the amount of s

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123