What are the temperature ranges for the supply and return water on the primary side and secondary side of the CDU?
Typical temperature range for the secondary supply water temperature is 12-18°C (54-65°F) with typical return of 18-24°C (64-75°F). Typical primary supply temperatures are in the range of 5-9°C (41-48°F) with return of 13-17°C (55-63°F). Contact Coolcentric to determine actual temperatures based on your site specific conditions.