Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the restrictions regarding the pumped refrigerant piping in Liebert XD?

0
Posted

What are the restrictions regarding the pumped refrigerant piping in Liebert XD?

0

The pumped refrigerant piping should be done with refrigerant quality brazing techniques, the piping should run overhead to allow a small piping slope from the modules back to the pumping unit (XDP) or the chiller (XDC). In general, the max distance between the XDP/XDC and the furthest located modules is 175 feet.