What are the requirements for submersible pumps or sumps?
Sump pumps and drains are not required in elevator pits. Sump holes must be installed and measure a minimum of eighteen inches by eighteen inches by eighteen inches. If drains or sump pumps are installed, they must not be directly connected to sewers and/or storm drains. P-traps and check valves are not allowed. All installations must meet the NEC and all plumbing codes. Drains meeting the above requirements may be installed in lieu of sump holes. Sump hole covers must be designed to withstand a load of three hundred pounds per square foot.