Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the requirements for power/electric for a Tech Logic sorting and/or delivery system?

0
Posted

What are the requirements for power/electric for a Tech Logic sorting and/or delivery system?

0

At locations specified on drawings, your library’s electrical contractor will need to provide the following: A 30, 60, 100 or 200 Amp (amperage dependant on individual system), 208 3 Phase, 5 wire service Cat6 Ethernet cables (with ends) from the remote nodes to the switch, and the same from the switch to the computer Wiring from the delivery control cabinets to the belt conveyor motors