Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the process plant requirements for Emerson Process Management devices used in SIS loops when IEC 61508 is applied?

0
10 Posted

What are the process plant requirements for Emerson Process Management devices used in SIS loops when IEC 61508 is applied?

0
10

When a plant implements IEC 61511 they will be required to use specific methodologies to document that the loop design meets the intended SIL level 1-4. These methodologies are quantitative and require specific data on each device per IEC 61508. The specific data required to determine Device SIL 1, 2, and 3 are documented in IEC61508 as follows: • Safe Failure Fraction (SFF) (Diagnostic Coverage Factors) • Safe Detected • Safe Undetected • Dangerous Detected • Dangerous Undetected • Mean time to repair • Frequency of Functional Check Requirements Rosemount publishes the required IEC 61508 data for their devices so that customers can calculate the SIS instrument loop value.