Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the minimum numbers of connectors that should be used in individual work area?

0
Posted

What are the minimum numbers of connectors that should be used in individual work area?

0

A minimum of two telecommunications outlets/connectors should be provided for each individual work areas. One telecommunications outlet/connector may be associated with voice, and the other with data. The two telecommunications outlets/connectors need to be configured as follows: One telecommunications outlet/connector must be supported by a four pair 100 Ohm cable that is rated Category 3 or higher (Category 5e recommended) The second telecommunications outlet/connector must be supported by a minimum of one of the following horizontal media. This media choice should be based on present and projected needs. Four-pair 100 Ohm Category 5e cable, or Two-fiber multimode optical fiber cable, either 62.5/125 micron or 50/125 micron. Single mode fiber 8.9 microns Two-pair 100 Ohm balanced twisted pair.