Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the minimum circuit breaker requirements for a Cisco 7500 Series Router DC power supply?

0
Posted

What are the minimum circuit breaker requirements for a Cisco 7500 Series Router DC power supply?

0

A. Size the breaker for the Cisco 7513 Series Router to deliver 40 A (amperes) to the system. The breaker for the Cisco 7507 Series Router must provide 24 A. You must respect local codes when you size breakers, but as a general rule of thumb you must have 25 percent extra current capacity. Therefore: • For the Cisco 7513 Series Router, choose the 50 A breaker. • For the Cisco 7505 Series Router, a breaker of 30 A is necessary. These sizes are based on the minimum input voltage of -40.5 Volts of Direct Current (VDC). Each of these systems has redundant power supplies as an option. Connect each supply to a separate breaker and branch to maintain redundancy.