What are the installation instructions for RS02 Average Room Temperature for measuring temperature in large rooms?
The following guidelines refer to Meitav-tec temperature sensor: Maximum Length with Shield Cable – Wire length for the remote sensor can be up to 30 meters with standard thermostat cable (not less than 22AWG). If distance is longer than 30 meters, then wire must be twisted and shielded, 20-22AWG. Cable must not pass by or be close to any High Voltage Lines or Devices. At 200 meters, resistance may affect temperature readings by one or two degrees.