Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the common failure modes of digital potentiometers?

0
Posted

What are the common failure modes of digital potentiometers?

0

1. Latch up can occur when the prescribed power-up sequence (VMDD->VMSS->GND->VA ->VB) is not followed. 2. A voltage greater than |VMDD – GND| or |VMDD – VMSS| (if dual-supply) applied across terminals A-B, W-B, or W-A can cause failure.

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123