Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What are the basic differences between API -661 and non-API coolers?

API BASIC coolers differences
0
Posted

What are the basic differences between API -661 and non-API coolers?

0

Sample differences required for API: – tube diameter minimum 1″ – geometry with regards to fan proximity to bundle – temperature limitations for considering split headers – lateral movement allowance of bundle – sloping on multi-pass condensers – header velocity limitations – minimum header material thickness – minimum nozzle dimensional tolerances, and maximum allowable nozzle loads – tube gauge minimums – restrictions on fan capacity, tip speeds, and motor minimum sizing – natural frequency, vibration limitations – minimum specifications on mechanical design of transmission components – louver minimal construction specifications – limitations on structural steel design, loads, and construction – minimum restrictions on welding procedures – specified noise measurement criteria and guidelines for winterization

Related Questions