What are QRF and PRF in the generator table?
For multiple generators regulating the same bus, this is the fraction of the total MVAR (QRF) or the total MW (PRF) to be served from the individual generator. For example, if generator 1 is 80 MVAR and generator 2 is 20 MVAR: The QRF factor is 80÷(20+80) = 0.8 for generator 1 The QRF factor is 20÷(20+80) = 0.2 for generator 2 If you enter a value of 1 for QRF, the PSLF software automatically adds the individual factors to obtain the total. If three units have a QRF of 1, each generator contributes 1/3 or 0.333 to the total MVAR. The PRF is used only for area interchange MW adjustment.