What Approvals do SECURIPLEX Systems carry?
• Protection of Combustion Turbines, Machinery Spaces, Special Hazard Machinery Spaces and Flammable Liquid Processing Hazards in Enclosures with Volumes not Exceeding 9175 ft3 (260 m3). • Protection of Wet Benches and Other Processing Equipment. • For Local Application Protection. FIRE-SCOPE 5000 (High Pressure, Single Fluid System) has the following approvals: • Protection of Combustion Turbines, Machinery Spaces, Special Hazard Machinery Spaces and Flammable Liquid Processing Hazards in Enclosures with Volumes Exceeding 9175 ft3 (260 m3). • Marine/VSCA Why is the water droplet size in a Water Mist System important? Smaller droplet sizes result in a more efficient use of the water. Water Mist works by flashing of the droplets to steam, resulting in reduction of the Oxygen content of the remaining air and cooling of the fire by causing loss of energy (steam production) and continued application of the water mist droplets. Smaller droplets have more surface area which increases the hea